What Is the Voltage Drop for 1 AWG at 20A and 300 Feet?

1 AWG at 20A and 300 feet: 1.85V drop (1.54% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

1 AWG, 20A, 300ft · single-phase / DC
1.85 V drop (1.54% on 120V)
On 120V circuit1.54%
On 240V circuit0.77%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
1.85V (1.54%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 20 × 0.154) ÷ 1000 = 1.85 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.85 ÷ 120) × 100 = 1.54%
On 240V: (1.85 ÷ 240) × 100 = 0.77%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 20A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.154V0.1283%0.0642%OK
50ft0.308V0.2567%0.1283%OK
75ft0.462V0.385%0.1925%OK
100ft0.616V0.5133%0.2567%OK
150ft0.924V0.77%0.385%OK
200ft1.23V1.03%0.5133%OK
300ft1.85V1.54%0.77%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 20A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 20A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG1.85V1.54%0.77%OK
1/0 AWG1.46V1.22%0.61%OK
2/0 AWG1.16V0.967%0.4835%OK
3/0 AWG0.9192V0.766%0.383%OK
4/0 AWG0.7296V0.608%0.304%OK
250 kcmil0.618V0.515%0.2575%OK

Frequently Asked Questions

1 AWG carrying 20A over 300ft has a 1.85V drop (1.54% on 120V). Reference: 0.77% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.77% on 240V versus 1.54% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (1.54% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.