What Is the Voltage Drop for 1 AWG at 20A and 400 Feet?

1 AWG copper carrying 20 amps over 400 feet on a single-phase / DC circuit drops 2.46 volts (2.05% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1 AWG, 20A, 400ft · single-phase / DC
2.46 V drop (2.05% on 120V)
On 120V circuit2.05%
On 240V circuit1.03%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
2.46V (2.05%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 400 × 20 × 0.154) ÷ 1000 = 2.46 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.46 ÷ 120) × 100 = 2.05%
On 240V: (2.46 ÷ 240) × 100 = 1.03%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 20A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.154V0.1283%0.0642%OK
50ft0.308V0.2567%0.1283%OK
75ft0.462V0.385%0.1925%OK
100ft0.616V0.5133%0.2567%OK
150ft0.924V0.77%0.385%OK
200ft1.23V1.03%0.5133%OK
300ft1.85V1.54%0.77%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 20A at 400 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 20A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG2.46V2.05%1.03%OK
1/0 AWG1.95V1.63%0.8133%OK
2/0 AWG1.55V1.29%0.6447%OK
3/0 AWG1.23V1.02%0.5107%OK
4/0 AWG0.9728V0.8107%0.4053%OK
250 kcmil0.824V0.6867%0.3433%OK

Frequently Asked Questions

1 AWG carrying 20A over 400ft has a 2.46V drop (2.05% on 120V). Reference: 1.03% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.03% on 240V versus 2.05% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.05%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.