What Is the Voltage Drop for 1 AWG at 34A and 50 Feet?

1 AWG copper carrying 34 amps over 50 feet on a single-phase / DC circuit drops 0.5236 volts (0.4363% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1 AWG, 34A, 50ft · single-phase / DC
0.5236 V drop (0.4363% on 120V)
On 120V circuit0.4363%
On 240V circuit0.2182%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
0.52V (0.44%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 34 × 0.154) ÷ 1000 = 0.5236 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5236 ÷ 120) × 100 = 0.4363%
On 240V: (0.5236 ÷ 240) × 100 = 0.2182%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 34A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2618V0.2182%0.1091%OK
50ft0.5236V0.4363%0.2182%OK
75ft0.7854V0.6545%0.3273%OK
100ft1.05V0.8727%0.4363%OK
150ft1.57V1.31%0.6545%OK
200ft2.09V1.75%0.8727%OK
300ft3.14V2.62%1.31%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 34A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 34A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG0.5236V0.4363%0.2182%OK
1/0 AWG0.4148V0.3457%0.1728%OK
2/0 AWG0.3288V0.274%0.137%OK
3/0 AWG0.2604V0.217%0.1085%OK
4/0 AWG0.2067V0.1723%0.0861%OK
250 kcmil0.1751V0.1459%0.073%OK

Frequently Asked Questions

1 AWG carrying 34A over 50ft has a 0.5236V drop (0.4363% on 120V). Reference: 0.2182% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (0.4363% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.4363%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.