What Is the Voltage Drop for 1 AWG at 35A and 75 Feet?
1 AWG at 35A and 75 feet: 0.8085V drop (0.6738% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 1 AWG at 35A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.2695V | 0.2246% | 0.1123% | OK |
| 50ft | 0.539V | 0.4492% | 0.2246% | OK |
| 75ft | 0.8085V | 0.6738% | 0.3369% | OK |
| 100ft | 1.08V | 0.8983% | 0.4492% | OK |
| 150ft | 1.62V | 1.35% | 0.6738% | OK |
| 200ft | 2.16V | 1.8% | 0.8983% | OK |
| 300ft | 3.23V | 2.7% | 1.35% | OK |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 35A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 35A load are listed, since thinner gauges would fail the ampacity check before drop even matters.