What Is the Voltage Drop for 1 AWG at 36A and 250 Feet?

Running 36A through 1 AWG copper for 250 feet on a single-phase / DC circuit produces a 2.77-volt drop. On a 120V source that is 2.31%; on 240V it is 1.16%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1 AWG, 36A, 250ft · single-phase / DC
2.77 V drop (2.31% on 120V)
On 120V circuit2.31%
On 240V circuit1.16%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
2.77V (2.31%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 36 × 0.154) ÷ 1000 = 2.77 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.77 ÷ 120) × 100 = 2.31%
On 240V: (2.77 ÷ 240) × 100 = 1.16%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 36A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2772V0.231%0.1155%OK
50ft0.5544V0.462%0.231%OK
75ft0.8316V0.693%0.3465%OK
100ft1.11V0.924%0.462%OK
150ft1.66V1.39%0.693%OK
200ft2.22V1.85%0.924%OK
300ft3.33V2.77%1.39%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 36A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 36A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG2.77V2.31%1.16%OK
1/0 AWG2.2V1.83%0.915%OK
2/0 AWG1.74V1.45%0.7253%OK
3/0 AWG1.38V1.15%0.5745%OK
4/0 AWG1.09V0.912%0.456%OK
250 kcmil0.927V0.7725%0.3863%OK

Frequently Asked Questions

1 AWG carrying 36A over 250ft has a 2.77V drop (2.31% on 120V). Reference: 1.16% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.31%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.16% on 240V versus 2.31% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.