What Is the Voltage Drop for 1 AWG at 40A and 300 Feet?

Running 40A through 1 AWG copper for 300 feet on a single-phase / DC circuit produces a 3.7-volt drop. On a 120V source that is 3.08%; on 240V it is 1.54%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1 AWG, 40A, 300ft · single-phase / DC
3.7 V drop (3.08% on 120V)
On 120V circuit3.08%
On 240V circuit1.54%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
3.70V (3.08%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 40 × 0.154) ÷ 1000 = 3.7 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.7 ÷ 120) × 100 = 3.08%
On 240V: (3.7 ÷ 240) × 100 = 1.54%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 40A over 300ft on 120V is 1/0 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 40A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.308V0.2567%0.1283%OK
50ft0.616V0.5133%0.2567%OK
75ft0.924V0.77%0.385%OK
100ft1.23V1.03%0.5133%OK
150ft1.85V1.54%0.77%OK
200ft2.46V2.05%1.03%OK
300ft3.7V3.08%1.54%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 40A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 40A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG3.7V3.08%1.54%Caution
1/0 AWG2.93V2.44%1.22%OK
2/0 AWG2.32V1.93%0.967%OK
3/0 AWG1.84V1.53%0.766%OK
4/0 AWG1.46V1.22%0.608%OK
250 kcmil1.24V1.03%0.515%OK

Frequently Asked Questions

1 AWG carrying 40A over 300ft has a 3.7V drop (3.08% on 120V). Reference: 1.54% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.54% on 240V versus 3.08% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 3.08%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.