What Is the Voltage Drop for 1 AWG at 59A and 25 Feet?

1 AWG copper carrying 59 amps over 25 feet on a single-phase / DC circuit drops 0.4543 volts (0.3786% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1 AWG, 59A, 25ft · single-phase / DC
0.4543 V drop (0.3786% on 120V)
On 120V circuit0.3786%
On 240V circuit0.1893%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
0.45V (0.38%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 59 × 0.154) ÷ 1000 = 0.4543 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.4543 ÷ 120) × 100 = 0.3786%
On 240V: (0.4543 ÷ 240) × 100 = 0.1893%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 59A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4543V0.3786%0.1893%OK
50ft0.9086V0.7572%0.3786%OK
75ft1.36V1.14%0.5679%OK
100ft1.82V1.51%0.7572%OK
150ft2.73V2.27%1.14%OK
200ft3.63V3.03%1.51%Caution
300ft5.45V4.54%2.27%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 59A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 59A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG0.4543V0.3786%0.1893%OK
1/0 AWG0.3599V0.2999%0.15%OK
2/0 AWG0.2853V0.2377%0.1189%OK
3/0 AWG0.226V0.1883%0.0942%OK
4/0 AWG0.1794V0.1495%0.0747%OK
250 kcmil0.1519V0.1266%0.0633%OK

Frequently Asked Questions

1 AWG carrying 59A over 25ft has a 0.4543V drop (0.3786% on 120V). Reference: 0.1893% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (0.3786% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.3786%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.