What Is the Voltage Drop for 1 AWG at 62A and 175 Feet?

1 AWG copper carrying 62 amps over 175 feet on a single-phase / DC circuit drops 3.34 volts (2.78% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1 AWG, 62A, 175ft · single-phase / DC
3.34 V drop (2.78% on 120V)
On 120V circuit2.78%
On 240V circuit1.39%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
3.34V (2.78%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 62 × 0.154) ÷ 1000 = 3.34 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.34 ÷ 120) × 100 = 2.78%
On 240V: (3.34 ÷ 240) × 100 = 1.39%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 62A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4774V0.3978%0.1989%OK
50ft0.9548V0.7957%0.3978%OK
75ft1.43V1.19%0.5968%OK
100ft1.91V1.59%0.7957%OK
150ft2.86V2.39%1.19%OK
200ft3.82V3.18%1.59%Caution
300ft5.73V4.77%2.39%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 62A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 62A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG3.34V2.78%1.39%OK
1/0 AWG2.65V2.21%1.1%OK
2/0 AWG2.1V1.75%0.8743%OK
3/0 AWG1.66V1.39%0.6926%OK
4/0 AWG1.32V1.1%0.5497%OK
250 kcmil1.12V0.9313%0.4656%OK

Frequently Asked Questions

1 AWG carrying 62A over 175ft has a 3.34V drop (2.78% on 120V). Reference: 1.39% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (2.78% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 2.78%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.