What Is the Voltage Drop for 1 AWG at 79A and 75 Feet?

Running 79A through 1 AWG copper for 75 feet on a single-phase / DC circuit produces a 1.82-volt drop. On a 120V source that is 1.52%; on 240V it is 0.7604%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1 AWG, 79A, 75ft · single-phase / DC
1.82 V drop (1.52% on 120V)
On 120V circuit1.52%
On 240V circuit0.7604%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
1.82V (1.52%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 79 × 0.154) ÷ 1000 = 1.82 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.82 ÷ 120) × 100 = 1.52%
On 240V: (1.82 ÷ 240) × 100 = 0.7604%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 79A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.6083V0.5069%0.2535%OK
50ft1.22V1.01%0.5069%OK
75ft1.82V1.52%0.7604%OK
100ft2.43V2.03%1.01%OK
150ft3.65V3.04%1.52%Caution
200ft4.87V4.06%2.03%Caution
300ft7.3V6.08%3.04%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 79A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 79A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG1.82V1.52%0.7604%OK
1/0 AWG1.45V1.2%0.6024%OK
2/0 AWG1.15V0.9549%0.4775%OK
3/0 AWG0.9077V0.7564%0.3782%OK
4/0 AWG0.7205V0.6004%0.3002%OK
250 kcmil0.6103V0.5086%0.2543%OK

Frequently Asked Questions

1 AWG carrying 79A over 75ft has a 1.82V drop (1.52% on 120V). Reference: 0.7604% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.7604% on 240V versus 1.52% on 120V.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (1.52% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 1.52%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.