What Is the Voltage Drop for 1 AWG at 89A and 50 Feet?

Running 89A through 1 AWG copper for 50 feet on a single-phase / DC circuit produces a 1.37-volt drop. On a 120V source that is 1.14%; on 240V it is 0.5711%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1 AWG, 89A, 50ft · single-phase / DC
1.37 V drop (1.14% on 120V)
On 120V circuit1.14%
On 240V circuit0.5711%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
1.37V (1.14%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 89 × 0.154) ÷ 1000 = 1.37 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.37 ÷ 120) × 100 = 1.14%
On 240V: (1.37 ÷ 240) × 100 = 0.5711%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 89A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.6853V0.5711%0.2855%OK
50ft1.37V1.14%0.5711%OK
75ft2.06V1.71%0.8566%OK
100ft2.74V2.28%1.14%OK
150ft4.11V3.43%1.71%Caution
200ft5.48V4.57%2.28%Caution
300ft8.22V6.85%3.43%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 89A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 89A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG1.37V1.14%0.5711%OK
1/0 AWG1.09V0.9048%0.4524%OK
2/0 AWG0.8606V0.7172%0.3586%OK
3/0 AWG0.6817V0.5681%0.2841%OK
4/0 AWG0.5411V0.4509%0.2255%OK
250 kcmil0.4584V0.382%0.191%OK

Frequently Asked Questions

1 AWG carrying 89A over 50ft has a 1.37V drop (1.14% on 120V). Reference: 0.5711% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.14%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.5711% on 240V versus 1.14% on 120V.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (1.14% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.