What Is the Voltage Drop for 1 AWG at 8A and 250 Feet?

1 AWG copper carrying 8 amps over 250 feet on a single-phase / DC circuit drops 0.616 volts (0.5133% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1 AWG, 8A, 250ft · single-phase / DC
0.616 V drop (0.5133% on 120V)
On 120V circuit0.5133%
On 240V circuit0.2567%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
0.62V (0.51%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 8 × 0.154) ÷ 1000 = 0.616 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.616 ÷ 120) × 100 = 0.5133%
On 240V: (0.616 ÷ 240) × 100 = 0.2567%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 8A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0616V0.0513%0.0257%OK
50ft0.1232V0.1027%0.0513%OK
75ft0.1848V0.154%0.077%OK
100ft0.2464V0.2053%0.1027%OK
150ft0.3696V0.308%0.154%OK
200ft0.4928V0.4107%0.2053%OK
300ft0.7392V0.616%0.308%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 8A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 8A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG0.616V0.5133%0.2567%OK
1/0 AWG0.488V0.4067%0.2033%OK
2/0 AWG0.3868V0.3223%0.1612%OK
3/0 AWG0.3064V0.2553%0.1277%OK
4/0 AWG0.2432V0.2027%0.1013%OK
250 kcmil0.206V0.1717%0.0858%OK

Frequently Asked Questions

1 AWG carrying 8A over 250ft has a 0.616V drop (0.5133% on 120V). Reference: 0.2567% on 240V.
On 120V, this run sits at 0.5133%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2567% on 240V versus 0.5133% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (0.5133% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.