What Is the Voltage Drop for 1 AWG at 9A and 75 Feet?

1 AWG copper carrying 9 amps over 75 feet on a single-phase / DC circuit drops 0.2079 volts (0.1733% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1 AWG, 9A, 75ft · single-phase / DC
0.2079 V drop (0.1733% on 120V)
On 120V circuit0.1733%
On 240V circuit0.0866%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
0.21V (0.17%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 9 × 0.154) ÷ 1000 = 0.2079 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.2079 ÷ 120) × 100 = 0.1733%
On 240V: (0.2079 ÷ 240) × 100 = 0.0866%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 9A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0693V0.0578%0.0289%OK
50ft0.1386V0.1155%0.0578%OK
75ft0.2079V0.1733%0.0866%OK
100ft0.2772V0.231%0.1155%OK
150ft0.4158V0.3465%0.1733%OK
200ft0.5544V0.462%0.231%OK
300ft0.8316V0.693%0.3465%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 9A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 9A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG0.2079V0.1733%0.0866%OK
1/0 AWG0.1647V0.1372%0.0686%OK
2/0 AWG0.1305V0.1088%0.0544%OK
3/0 AWG0.1034V0.0862%0.0431%OK
4/0 AWG0.0821V0.0684%0.0342%OK
250 kcmil0.0695V0.0579%0.029%OK

Frequently Asked Questions

1 AWG carrying 9A over 75ft has a 0.2079V drop (0.1733% on 120V). Reference: 0.0866% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (0.1733% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.1733%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.