What Is the Voltage Drop for 2 AWG at 108A and 25 Feet?

Running 108A through 2 AWG copper for 25 feet on a single-phase / DC circuit produces a 1.05-volt drop. On a 120V source that is 0.873%; on 240V it is 0.4365%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2 AWG, 108A, 25ft · single-phase / DC
1.05 V drop (0.873% on 120V)
On 120V circuit0.873%
On 240V circuit0.4365%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
1.05V (0.87%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 108 × 0.194) ÷ 1000 = 1.05 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.05 ÷ 120) × 100 = 0.873%
On 240V: (1.05 ÷ 240) × 100 = 0.4365%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 108A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.05V0.873%0.4365%OK
50ft2.1V1.75%0.873%OK
75ft3.14V2.62%1.31%OK
100ft4.19V3.49%1.75%Caution
150ft6.29V5.24%2.62%Past 5%
200ft8.38V6.98%3.49%Past 5%
300ft12.57V10.48%5.24%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 108A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 108A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG1.05V0.873%0.4365%OK
1 AWG0.8316V0.693%0.3465%OK
1/0 AWG0.6588V0.549%0.2745%OK
2/0 AWG0.5222V0.4351%0.2176%OK
3/0 AWG0.4136V0.3447%0.1724%OK
4/0 AWG0.3283V0.2736%0.1368%OK

Frequently Asked Questions

2 AWG carrying 108A over 25ft has a 1.05V drop (0.873% on 120V). Reference: 0.4365% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (0.873% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.873%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.4365% on 240V versus 0.873% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.