What Is the Voltage Drop for 2 AWG at 109A and 25 Feet?
2 AWG at 109A and 25 feet: 1.06V drop (0.8811% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 2 AWG at 109A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 1.06V | 0.8811% | 0.4405% | OK |
| 50ft | 2.11V | 1.76% | 0.8811% | OK |
| 75ft | 3.17V | 2.64% | 1.32% | OK |
| 100ft | 4.23V | 3.52% | 1.76% | Caution |
| 150ft | 6.34V | 5.29% | 2.64% | Past 5% |
| 200ft | 8.46V | 7.05% | 3.52% | Past 5% |
| 300ft | 12.69V | 10.57% | 5.29% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 109A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 109A load are listed, since thinner gauges would fail the ampacity check before drop even matters.