What Is the Voltage Drop for 2 AWG at 16A and 125 Feet?

2 AWG copper carrying 16 amps over 125 feet on a single-phase / DC circuit drops 0.776 volts (0.6467% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2 AWG, 16A, 125ft · single-phase / DC
0.776 V drop (0.6467% on 120V)
On 120V circuit0.6467%
On 240V circuit0.3233%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
0.78V (0.65%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 16 × 0.194) ÷ 1000 = 0.776 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.776 ÷ 120) × 100 = 0.6467%
On 240V: (0.776 ÷ 240) × 100 = 0.3233%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 16A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1552V0.1293%0.0647%OK
50ft0.3104V0.2587%0.1293%OK
75ft0.4656V0.388%0.194%OK
100ft0.6208V0.5173%0.2587%OK
150ft0.9312V0.776%0.388%OK
200ft1.24V1.03%0.5173%OK
300ft1.86V1.55%0.776%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 16A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 16A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG0.776V0.6467%0.3233%OK
1 AWG0.616V0.5133%0.2567%OK
1/0 AWG0.488V0.4067%0.2033%OK
2/0 AWG0.3868V0.3223%0.1612%OK
3/0 AWG0.3064V0.2553%0.1277%OK
4/0 AWG0.2432V0.2027%0.1013%OK

Frequently Asked Questions

2 AWG carrying 16A over 125ft has a 0.776V drop (0.6467% on 120V). Reference: 0.3233% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 0.6467%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (0.6467% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3233% on 240V versus 0.6467% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.