What Is the Voltage Drop for 2 AWG at 19A and 400 Feet?

2 AWG at 19A and 400 feet: 2.95V drop (2.46% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2 AWG, 19A, 400ft · single-phase / DC
2.95 V drop (2.46% on 120V)
On 120V circuit2.46%
On 240V circuit1.23%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
2.95V (2.46%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 400 × 19 × 0.194) ÷ 1000 = 2.95 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.95 ÷ 120) × 100 = 2.46%
On 240V: (2.95 ÷ 240) × 100 = 1.23%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 19A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1843V0.1536%0.0768%OK
50ft0.3686V0.3072%0.1536%OK
75ft0.5529V0.4607%0.2304%OK
100ft0.7372V0.6143%0.3072%OK
150ft1.11V0.9215%0.4607%OK
200ft1.47V1.23%0.6143%OK
300ft2.21V1.84%0.9215%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 19A at 400 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 19A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG2.95V2.46%1.23%OK
1 AWG2.34V1.95%0.9753%OK
1/0 AWG1.85V1.55%0.7727%OK
2/0 AWG1.47V1.22%0.6124%OK
3/0 AWG1.16V0.9703%0.4851%OK
4/0 AWG0.9242V0.7701%0.3851%OK

Frequently Asked Questions

2 AWG carrying 19A over 400ft has a 2.95V drop (2.46% on 120V). Reference: 1.23% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.23% on 240V versus 2.46% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.46%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.