What Is the Voltage Drop for 2 AWG at 28A and 300 Feet?

Running 28A through 2 AWG copper for 300 feet on a single-phase / DC circuit produces a 3.26-volt drop. On a 120V source that is 2.72%; on 240V it is 1.36%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2 AWG, 28A, 300ft · single-phase / DC
3.26 V drop (2.72% on 120V)
On 120V circuit2.72%
On 240V circuit1.36%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
3.26V (2.72%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 28 × 0.194) ÷ 1000 = 3.26 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.26 ÷ 120) × 100 = 2.72%
On 240V: (3.26 ÷ 240) × 100 = 1.36%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 28A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2716V0.2263%0.1132%OK
50ft0.5432V0.4527%0.2263%OK
75ft0.8148V0.679%0.3395%OK
100ft1.09V0.9053%0.4527%OK
150ft1.63V1.36%0.679%OK
200ft2.17V1.81%0.9053%OK
300ft3.26V2.72%1.36%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 28A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 28A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG3.26V2.72%1.36%OK
1 AWG2.59V2.16%1.08%OK
1/0 AWG2.05V1.71%0.854%OK
2/0 AWG1.62V1.35%0.6769%OK
3/0 AWG1.29V1.07%0.5362%OK
4/0 AWG1.02V0.8512%0.4256%OK

Frequently Asked Questions

2 AWG carrying 28A over 300ft has a 3.26V drop (2.72% on 120V). Reference: 1.36% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.72%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (2.72% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Yes. Aluminum has roughly 1.3 to 1.4 times the resistance of copper at the NEC Chapter 9 Table 8 75°C reference temperature, so for the same voltage drop an aluminum conductor is typically one to two gauges larger than copper. The exact gap depends on whether ampacity or voltage drop is binding, and the install still needs anti-oxidant compound and aluminum-rated lugs.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.