What Is the Voltage Drop for 2 AWG at 33A and 50 Feet?

2 AWG at 33A and 50 feet: 0.6402V drop (0.5335% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2 AWG, 33A, 50ft · single-phase / DC
0.6402 V drop (0.5335% on 120V)
On 120V circuit0.5335%
On 240V circuit0.2668%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
0.64V (0.53%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 33 × 0.194) ÷ 1000 = 0.6402 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.6402 ÷ 120) × 100 = 0.5335%
On 240V: (0.6402 ÷ 240) × 100 = 0.2668%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 33A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3201V0.2668%0.1334%OK
50ft0.6402V0.5335%0.2668%OK
75ft0.9603V0.8003%0.4001%OK
100ft1.28V1.07%0.5335%OK
150ft1.92V1.6%0.8003%OK
200ft2.56V2.13%1.07%OK
300ft3.84V3.2%1.6%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 33A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 33A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG0.6402V0.5335%0.2668%OK
1 AWG0.5082V0.4235%0.2118%OK
1/0 AWG0.4026V0.3355%0.1677%OK
2/0 AWG0.3191V0.2659%0.133%OK
3/0 AWG0.2528V0.2106%0.1053%OK
4/0 AWG0.2006V0.1672%0.0836%OK

Frequently Asked Questions

2 AWG carrying 33A over 50ft has a 0.6402V drop (0.5335% on 120V). Reference: 0.2668% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (0.5335% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.5335%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.