What Is the Voltage Drop for 2 AWG at 44A and 75 Feet?

2 AWG at 44A and 75 feet: 1.28V drop (1.07% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2 AWG, 44A, 75ft · single-phase / DC
1.28 V drop (1.07% on 120V)
On 120V circuit1.07%
On 240V circuit0.5335%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
1.28V (1.07%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 44 × 0.194) ÷ 1000 = 1.28 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.28 ÷ 120) × 100 = 1.07%
On 240V: (1.28 ÷ 240) × 100 = 0.5335%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 44A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4268V0.3557%0.1778%OK
50ft0.8536V0.7113%0.3557%OK
75ft1.28V1.07%0.5335%OK
100ft1.71V1.42%0.7113%OK
150ft2.56V2.13%1.07%OK
200ft3.41V2.85%1.42%OK
300ft5.12V4.27%2.13%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 44A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 44A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG1.28V1.07%0.5335%OK
1 AWG1.02V0.847%0.4235%OK
1/0 AWG0.8052V0.671%0.3355%OK
2/0 AWG0.6382V0.5318%0.2659%OK
3/0 AWG0.5056V0.4213%0.2106%OK
4/0 AWG0.4013V0.3344%0.1672%OK

Frequently Asked Questions

2 AWG carrying 44A over 75ft has a 1.28V drop (1.07% on 120V). Reference: 0.5335% on 240V.
On 120V, this run sits at 1.07%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.5335% on 240V versus 1.07% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.