What Is the Voltage Drop for 2 AWG at 49A and 150 Feet?

Running 49A through 2 AWG copper for 150 feet on a single-phase / DC circuit produces a 2.85-volt drop. On a 120V source that is 2.38%; on 240V it is 1.19%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2 AWG, 49A, 150ft · single-phase / DC
2.85 V drop (2.38% on 120V)
On 120V circuit2.38%
On 240V circuit1.19%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
2.85V (2.38%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 150 × 49 × 0.194) ÷ 1000 = 2.85 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.85 ÷ 120) × 100 = 2.38%
On 240V: (2.85 ÷ 240) × 100 = 1.19%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 49A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4753V0.3961%0.198%OK
50ft0.9506V0.7922%0.3961%OK
75ft1.43V1.19%0.5941%OK
100ft1.9V1.58%0.7922%OK
150ft2.85V2.38%1.19%OK
200ft3.8V3.17%1.58%Caution
300ft5.7V4.75%2.38%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 49A at 150 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 49A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG2.85V2.38%1.19%OK
1 AWG2.26V1.89%0.9433%OK
1/0 AWG1.79V1.49%0.7472%OK
2/0 AWG1.42V1.18%0.5923%OK
3/0 AWG1.13V0.9383%0.4692%OK
4/0 AWG0.8938V0.7448%0.3724%OK

Frequently Asked Questions

2 AWG carrying 49A over 150ft has a 2.85V drop (2.38% on 120V). Reference: 1.19% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.19% on 240V versus 2.38% on 120V.
On 120V, this run sits at 2.38%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (2.38% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.