What Is the Voltage Drop for 2 AWG at 53A and 100 Feet?

2 AWG copper carrying 53 amps over 100 feet on a single-phase / DC circuit drops 2.06 volts (1.71% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2 AWG, 53A, 100ft · single-phase / DC
2.06 V drop (1.71% on 120V)
On 120V circuit1.71%
On 240V circuit0.8568%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
2.06V (1.71%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 53 × 0.194) ÷ 1000 = 2.06 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.06 ÷ 120) × 100 = 1.71%
On 240V: (2.06 ÷ 240) × 100 = 0.8568%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 53A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5141V0.4284%0.2142%OK
50ft1.03V0.8568%0.4284%OK
75ft1.54V1.29%0.6426%OK
100ft2.06V1.71%0.8568%OK
150ft3.08V2.57%1.29%OK
200ft4.11V3.43%1.71%Caution
300ft6.17V5.14%2.57%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 53A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 53A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG2.06V1.71%0.8568%OK
1 AWG1.63V1.36%0.6802%OK
1/0 AWG1.29V1.08%0.5388%OK
2/0 AWG1.03V0.8542%0.4271%OK
3/0 AWG0.812V0.6766%0.3383%OK
4/0 AWG0.6445V0.5371%0.2685%OK

Frequently Asked Questions

2 AWG carrying 53A over 100ft has a 2.06V drop (1.71% on 120V). Reference: 0.8568% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.8568% on 240V versus 1.71% on 120V.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (1.71% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 1.71%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.