What Is the Voltage Drop for 2 AWG at 57A and 100 Feet?

Running 57A through 2 AWG copper for 100 feet on a single-phase / DC circuit produces a 2.21-volt drop. On a 120V source that is 1.84%; on 240V it is 0.9215%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2 AWG, 57A, 100ft · single-phase / DC
2.21 V drop (1.84% on 120V)
On 120V circuit1.84%
On 240V circuit0.9215%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
2.21V (1.84%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 57 × 0.194) ÷ 1000 = 2.21 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.21 ÷ 120) × 100 = 1.84%
On 240V: (2.21 ÷ 240) × 100 = 0.9215%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 57A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5529V0.4607%0.2304%OK
50ft1.11V0.9215%0.4607%OK
75ft1.66V1.38%0.6911%OK
100ft2.21V1.84%0.9215%OK
150ft3.32V2.76%1.38%OK
200ft4.42V3.69%1.84%Caution
300ft6.63V5.53%2.76%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 57A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 57A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG2.21V1.84%0.9215%OK
1 AWG1.76V1.46%0.7315%OK
1/0 AWG1.39V1.16%0.5795%OK
2/0 AWG1.1V0.9186%0.4593%OK
3/0 AWG0.8732V0.7277%0.3639%OK
4/0 AWG0.6931V0.5776%0.2888%OK

Frequently Asked Questions

2 AWG carrying 57A over 100ft has a 2.21V drop (1.84% on 120V). Reference: 0.9215% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.84%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9215% on 240V versus 1.84% on 120V.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (1.84% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.