What Is the Voltage Drop for 2 AWG at 58A and 75 Feet?

Running 58A through 2 AWG copper for 75 feet on a single-phase / DC circuit produces a 1.69-volt drop. On a 120V source that is 1.41%; on 240V it is 0.7032%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

2 AWG, 58A, 75ft · single-phase / DC
1.69 V drop (1.41% on 120V)
On 120V circuit1.41%
On 240V circuit0.7032%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
1.69V (1.41%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 58 × 0.194) ÷ 1000 = 1.69 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.69 ÷ 120) × 100 = 1.41%
On 240V: (1.69 ÷ 240) × 100 = 0.7032%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 58A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5626V0.4688%0.2344%OK
50ft1.13V0.9377%0.4688%OK
75ft1.69V1.41%0.7032%OK
100ft2.25V1.88%0.9377%OK
150ft3.38V2.81%1.41%OK
200ft4.5V3.75%1.88%Caution
300ft6.75V5.63%2.81%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 58A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 58A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG1.69V1.41%0.7032%OK
1 AWG1.34V1.12%0.5583%OK
1/0 AWG1.06V0.8845%0.4422%OK
2/0 AWG0.8413V0.7011%0.3505%OK
3/0 AWG0.6664V0.5554%0.2777%OK
4/0 AWG0.529V0.4408%0.2204%OK

Frequently Asked Questions

2 AWG carrying 58A over 75ft has a 1.69V drop (1.41% on 120V). Reference: 0.7032% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (1.41% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 1.41%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.7032% on 240V versus 1.41% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.