What Is the Voltage Drop for 2 AWG at 6A and 500 Feet?

2 AWG at 6A and 500 feet: 1.16V drop (0.97% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2 AWG, 6A, 500ft · single-phase / DC
1.16 V drop (0.97% on 120V)
On 120V circuit0.97%
On 240V circuit0.485%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
1.16V (0.97%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 6 × 0.194) ÷ 1000 = 1.16 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.16 ÷ 120) × 100 = 0.97%
On 240V: (1.16 ÷ 240) × 100 = 0.485%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 6A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0582V0.0485%0.0243%OK
50ft0.1164V0.097%0.0485%OK
75ft0.1746V0.1455%0.0728%OK
100ft0.2328V0.194%0.097%OK
150ft0.3492V0.291%0.1455%OK
200ft0.4656V0.388%0.194%OK
300ft0.6984V0.582%0.291%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 6A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 6A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG1.16V0.97%0.485%OK
1 AWG0.924V0.77%0.385%OK
1/0 AWG0.732V0.61%0.305%OK
2/0 AWG0.5802V0.4835%0.2418%OK
3/0 AWG0.4596V0.383%0.1915%OK
4/0 AWG0.3648V0.304%0.152%OK

Frequently Asked Questions

2 AWG carrying 6A over 500ft has a 1.16V drop (0.97% on 120V). Reference: 0.485% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.485% on 240V versus 0.97% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.97%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.