What Is the Voltage Drop for 2 AWG at 78A and 75 Feet?

2 AWG copper carrying 78 amps over 75 feet on a single-phase / DC circuit drops 2.27 volts (1.89% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

2 AWG, 78A, 75ft · single-phase / DC
2.27 V drop (1.89% on 120V)
On 120V circuit1.89%
On 240V circuit0.9458%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
2.27V (1.89%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 78 × 0.194) ÷ 1000 = 2.27 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.27 ÷ 120) × 100 = 1.89%
On 240V: (2.27 ÷ 240) × 100 = 0.9458%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 78A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.7566V0.6305%0.3153%OK
50ft1.51V1.26%0.6305%OK
75ft2.27V1.89%0.9458%OK
100ft3.03V2.52%1.26%OK
150ft4.54V3.78%1.89%Caution
200ft6.05V5.04%2.52%Past 5%
300ft9.08V7.57%3.78%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 78A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 78A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG2.27V1.89%0.9458%OK
1 AWG1.8V1.5%0.7507%OK
1/0 AWG1.43V1.19%0.5947%OK
2/0 AWG1.13V0.9428%0.4714%OK
3/0 AWG0.8962V0.7469%0.3734%OK
4/0 AWG0.7114V0.5928%0.2964%OK

Frequently Asked Questions

2 AWG carrying 78A over 75ft has a 2.27V drop (1.89% on 120V). Reference: 0.9458% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9458% on 240V versus 1.89% on 120V.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (1.89% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 1.89%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.