What Is the Voltage Drop for 2 AWG at 90A and 50 Feet?

2 AWG at 90A and 50 feet: 1.75V drop (1.46% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

2 AWG, 90A, 50ft · single-phase / DC
1.75 V drop (1.46% on 120V)
On 120V circuit1.46%
On 240V circuit0.7275%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

2 AWG
1.75V (1.46%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 90 × 0.194) ÷ 1000 = 1.75 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.75 ÷ 120) × 100 = 1.46%
On 240V: (1.75 ÷ 240) × 100 = 0.7275%

How This Estimate Changes with Run Length and Gauge

Gauge Check

2 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 2 AWG at 90A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.873V0.7275%0.3638%OK
50ft1.75V1.46%0.7275%OK
75ft2.62V2.18%1.09%OK
100ft3.49V2.91%1.46%OK
150ft5.24V4.37%2.18%Caution
200ft6.98V5.82%2.91%Past 5%
300ft10.48V8.73%4.37%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 90A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 90A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
2 AWG1.75V1.46%0.7275%OK
1 AWG1.39V1.16%0.5775%OK
1/0 AWG1.1V0.915%0.4575%OK
2/0 AWG0.8703V0.7253%0.3626%OK
3/0 AWG0.6894V0.5745%0.2873%OK
4/0 AWG0.5472V0.456%0.228%OK

Frequently Asked Questions

2 AWG carrying 90A over 50ft has a 1.75V drop (1.46% on 120V). Reference: 0.7275% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.7275% on 240V versus 1.46% on 120V.
On 120V, this run sits at 1.46%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
2 AWG already sits within the 3% branch-circuit drop target at these inputs (1.46% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.