What Is the Voltage Drop for 3/0 AWG at 112A and 25 Feet?

3/0 AWG at 112A and 25 feet: 0.429V drop (0.3575% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

3/0 AWG, 112A, 25ft · single-phase / DC
0.429 V drop (0.3575% on 120V)
On 120V circuit0.3575%
On 240V circuit0.1787%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
0.43V (0.36%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 112 × 0.0766) ÷ 1000 = 0.429 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.429 ÷ 120) × 100 = 0.3575%
On 240V: (0.429 ÷ 240) × 100 = 0.1787%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 112A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.429V0.3575%0.1787%OK
50ft0.8579V0.7149%0.3575%OK
75ft1.29V1.07%0.5362%OK
100ft1.72V1.43%0.7149%OK
150ft2.57V2.14%1.07%OK
200ft3.43V2.86%1.43%OK
300ft5.15V4.29%2.14%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 112A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 112A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG0.429V0.3575%0.1787%OK
4/0 AWG0.3405V0.2837%0.1419%OK
250 kcmil0.2884V0.2403%0.1202%OK
300 kcmil0.2402V0.2002%0.1001%OK
350 kcmil0.2055V0.1713%0.0856%OK
500 kcmil0.1445V0.1204%0.0602%OK

Frequently Asked Questions

3/0 AWG carrying 112A over 25ft has a 0.429V drop (0.3575% on 120V). Reference: 0.1787% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.3575% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.3575%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.1787% on 240V versus 0.3575% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.