What Is the Voltage Drop for 3/0 AWG at 118A and 150 Feet?

Running 118A through 3/0 AWG copper for 150 feet on a single-phase / DC circuit produces a 2.71-volt drop. On a 120V source that is 2.26%; on 240V it is 1.13%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3/0 AWG, 118A, 150ft · single-phase / DC
2.71 V drop (2.26% on 120V)
On 120V circuit2.26%
On 240V circuit1.13%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
2.71V (2.26%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 150 × 118 × 0.0766) ÷ 1000 = 2.71 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.71 ÷ 120) × 100 = 2.26%
On 240V: (2.71 ÷ 240) × 100 = 1.13%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 118A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4519V0.3766%0.1883%OK
50ft0.9039V0.7532%0.3766%OK
75ft1.36V1.13%0.5649%OK
100ft1.81V1.51%0.7532%OK
150ft2.71V2.26%1.13%OK
200ft3.62V3.01%1.51%Caution
300ft5.42V4.52%2.26%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 118A at 150 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 118A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG2.71V2.26%1.13%OK
4/0 AWG2.15V1.79%0.8968%OK
250 kcmil1.82V1.52%0.7596%OK
300 kcmil1.52V1.27%0.6328%OK
350 kcmil1.3V1.08%0.5413%OK
500 kcmil0.9133V0.7611%0.3806%OK

Frequently Asked Questions

3/0 AWG carrying 118A over 150ft has a 2.71V drop (2.26% on 120V). Reference: 1.13% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.26%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.13% on 240V versus 2.26% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.