What Is the Voltage Drop for 3/0 AWG at 12A and 125 Feet?

3/0 AWG at 12A and 125 feet: 0.2298V drop (0.1915% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

3/0 AWG, 12A, 125ft · single-phase / DC
0.2298 V drop (0.1915% on 120V)
On 120V circuit0.1915%
On 240V circuit0.0958%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
0.23V (0.19%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 12 × 0.0766) ÷ 1000 = 0.2298 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.2298 ÷ 120) × 100 = 0.1915%
On 240V: (0.2298 ÷ 240) × 100 = 0.0958%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 12A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.046V0.0383%0.0192%OK
50ft0.0919V0.0766%0.0383%OK
75ft0.1379V0.1149%0.0575%OK
100ft0.1838V0.1532%0.0766%OK
150ft0.2758V0.2298%0.1149%OK
200ft0.3677V0.3064%0.1532%OK
300ft0.5515V0.4596%0.2298%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 12A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 12A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG0.2298V0.1915%0.0958%OK
4/0 AWG0.1824V0.152%0.076%OK
250 kcmil0.1545V0.1288%0.0644%OK
300 kcmil0.1287V0.1072%0.0536%OK
350 kcmil0.1101V0.0918%0.0459%OK
500 kcmil0.0774V0.0645%0.0323%OK

Frequently Asked Questions

3/0 AWG carrying 12A over 125ft has a 0.2298V drop (0.1915% on 120V). Reference: 0.0958% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.1915% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.1915%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.0958% on 240V versus 0.1915% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.