What Is the Voltage Drop for 3/0 AWG at 18A and 500 Feet?

3/0 AWG at 18A and 500 feet: 1.38V drop (1.15% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

3/0 AWG, 18A, 500ft · single-phase / DC
1.38 V drop (1.15% on 120V)
On 120V circuit1.15%
On 240V circuit0.5745%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
1.38V (1.15%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 18 × 0.0766) ÷ 1000 = 1.38 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.38 ÷ 120) × 100 = 1.15%
On 240V: (1.38 ÷ 240) × 100 = 0.5745%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 18A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0689V0.0575%0.0287%OK
50ft0.1379V0.1149%0.0575%OK
75ft0.2068V0.1724%0.0862%OK
100ft0.2758V0.2298%0.1149%OK
150ft0.4136V0.3447%0.1724%OK
200ft0.5515V0.4596%0.2298%OK
300ft0.8273V0.6894%0.3447%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 18A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 18A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG1.38V1.15%0.5745%OK
4/0 AWG1.09V0.912%0.456%OK
250 kcmil0.927V0.7725%0.3863%OK
300 kcmil0.7722V0.6435%0.3218%OK
350 kcmil0.6606V0.5505%0.2753%OK
500 kcmil0.4644V0.387%0.1935%OK

Frequently Asked Questions

3/0 AWG carrying 18A over 500ft has a 1.38V drop (1.15% on 120V). Reference: 0.5745% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.15%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.5745% on 240V versus 1.15% on 120V.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.15% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.