What Is the Voltage Drop for 3/0 AWG at 193A and 75 Feet?

Running 193A through 3/0 AWG copper for 75 feet on a single-phase / DC circuit produces a 2.22-volt drop. On a 120V source that is 1.85%; on 240V it is 0.924%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3/0 AWG, 193A, 75ft · single-phase / DC
2.22 V drop (1.85% on 120V)
On 120V circuit1.85%
On 240V circuit0.924%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
2.22V (1.85%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 193 × 0.0766) ÷ 1000 = 2.22 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.22 ÷ 120) × 100 = 1.85%
On 240V: (2.22 ÷ 240) × 100 = 0.924%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 193A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.7392V0.616%0.308%OK
50ft1.48V1.23%0.616%OK
75ft2.22V1.85%0.924%OK
100ft2.96V2.46%1.23%OK
150ft4.44V3.7%1.85%Caution
200ft5.91V4.93%2.46%Caution
300ft8.87V7.39%3.7%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 193A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 193A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG2.22V1.85%0.924%OK
4/0 AWG1.76V1.47%0.7334%OK
250 kcmil1.49V1.24%0.6212%OK
300 kcmil1.24V1.03%0.5175%OK
350 kcmil1.06V0.8854%0.4427%OK
500 kcmil0.7469V0.6224%0.3112%OK

Frequently Asked Questions

3/0 AWG carrying 193A over 75ft has a 2.22V drop (1.85% on 120V). Reference: 0.924% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.85%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.924% on 240V versus 1.85% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.