What Is the Voltage Drop for 3/0 AWG at 194A and 100 Feet?

3/0 AWG copper carrying 194 amps over 100 feet on a single-phase / DC circuit drops 2.97 volts (2.48% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3/0 AWG, 194A, 100ft · single-phase / DC
2.97 V drop (2.48% on 120V)
On 120V circuit2.48%
On 240V circuit1.24%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
2.97V (2.48%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 194 × 0.0766) ÷ 1000 = 2.97 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.97 ÷ 120) × 100 = 2.48%
On 240V: (2.97 ÷ 240) × 100 = 1.24%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 194A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.743V0.6192%0.3096%OK
50ft1.49V1.24%0.6192%OK
75ft2.23V1.86%0.9288%OK
100ft2.97V2.48%1.24%OK
150ft4.46V3.72%1.86%Caution
200ft5.94V4.95%2.48%Caution
300ft8.92V7.43%3.72%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 194A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 194A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG2.97V2.48%1.24%OK
4/0 AWG2.36V1.97%0.9829%OK
250 kcmil2V1.67%0.8326%OK
300 kcmil1.66V1.39%0.6936%OK
350 kcmil1.42V1.19%0.5933%OK
500 kcmil1V0.8342%0.4171%OK

Frequently Asked Questions

3/0 AWG carrying 194A over 100ft has a 2.97V drop (2.48% on 120V). Reference: 1.24% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.24% on 240V versus 2.48% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.48% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.