What Is the Voltage Drop for 3/0 AWG at 39A and 250 Feet?

Running 39A through 3/0 AWG copper for 250 feet on a single-phase / DC circuit produces a 1.49-volt drop. On a 120V source that is 1.24%; on 240V it is 0.6224%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3/0 AWG, 39A, 250ft · single-phase / DC
1.49 V drop (1.24% on 120V)
On 120V circuit1.24%
On 240V circuit0.6224%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
1.49V (1.24%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 39 × 0.0766) ÷ 1000 = 1.49 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.49 ÷ 120) × 100 = 1.24%
On 240V: (1.49 ÷ 240) × 100 = 0.6224%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 39A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1494V0.1245%0.0622%OK
50ft0.2987V0.249%0.1245%OK
75ft0.4481V0.3734%0.1867%OK
100ft0.5975V0.4979%0.249%OK
150ft0.8962V0.7469%0.3734%OK
200ft1.19V0.9958%0.4979%OK
300ft1.79V1.49%0.7469%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 39A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 39A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG1.49V1.24%0.6224%OK
4/0 AWG1.19V0.988%0.494%OK
250 kcmil1V0.8369%0.4184%OK
300 kcmil0.8366V0.6971%0.3486%OK
350 kcmil0.7157V0.5964%0.2982%OK
500 kcmil0.5031V0.4193%0.2096%OK

Frequently Asked Questions

3/0 AWG carrying 39A over 250ft has a 1.49V drop (1.24% on 120V). Reference: 0.6224% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.24%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.6224% on 240V versus 1.24% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.