What Is the Voltage Drop for 3/0 AWG at 46A and 25 Feet?

3/0 AWG at 46A and 25 feet: 0.1762V drop (0.1468% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

3/0 AWG, 46A, 25ft · single-phase / DC
0.1762 V drop (0.1468% on 120V)
On 120V circuit0.1468%
On 240V circuit0.0734%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
0.18V (0.15%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 46 × 0.0766) ÷ 1000 = 0.1762 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.1762 ÷ 120) × 100 = 0.1468%
On 240V: (0.1762 ÷ 240) × 100 = 0.0734%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 46A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1762V0.1468%0.0734%OK
50ft0.3524V0.2936%0.1468%OK
75ft0.5285V0.4405%0.2202%OK
100ft0.7047V0.5873%0.2936%OK
150ft1.06V0.8809%0.4405%OK
200ft1.41V1.17%0.5873%OK
300ft2.11V1.76%0.8809%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 46A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 46A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG0.1762V0.1468%0.0734%OK
4/0 AWG0.1398V0.1165%0.0583%OK
250 kcmil0.1184V0.0987%0.0494%OK
300 kcmil0.0987V0.0822%0.0411%OK
350 kcmil0.0844V0.0703%0.0352%OK
500 kcmil0.0593V0.0495%0.0247%OK

Frequently Asked Questions

3/0 AWG carrying 46A over 25ft has a 0.1762V drop (0.1468% on 120V). Reference: 0.0734% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.1468% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.1468%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.