What Is the Voltage Drop for 3/0 AWG at 49A and 300 Feet?

Running 49A through 3/0 AWG copper for 300 feet on a single-phase / DC circuit produces a 2.25-volt drop. On a 120V source that is 1.88%; on 240V it is 0.9383%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3/0 AWG, 49A, 300ft · single-phase / DC
2.25 V drop (1.88% on 120V)
On 120V circuit1.88%
On 240V circuit0.9383%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
2.25V (1.88%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 49 × 0.0766) ÷ 1000 = 2.25 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.25 ÷ 120) × 100 = 1.88%
On 240V: (2.25 ÷ 240) × 100 = 0.9383%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 49A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1877V0.1564%0.0782%OK
50ft0.3753V0.3128%0.1564%OK
75ft0.563V0.4692%0.2346%OK
100ft0.7507V0.6256%0.3128%OK
150ft1.13V0.9383%0.4692%OK
200ft1.5V1.25%0.6256%OK
300ft2.25V1.88%0.9383%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 49A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 49A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG2.25V1.88%0.9383%OK
4/0 AWG1.79V1.49%0.7448%OK
250 kcmil1.51V1.26%0.6309%OK
300 kcmil1.26V1.05%0.5255%OK
350 kcmil1.08V0.8992%0.4496%OK
500 kcmil0.7585V0.6321%0.316%OK

Frequently Asked Questions

3/0 AWG carrying 49A over 300ft has a 2.25V drop (1.88% on 120V). Reference: 0.9383% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9383% on 240V versus 1.88% on 120V.
On 120V, this run sits at 1.88%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.88% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.