What Is the Voltage Drop for 3/0 AWG at 58A and 400 Feet?

3/0 AWG at 58A and 400 feet: 3.55V drop (2.96% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

3/0 AWG, 58A, 400ft · single-phase / DC
3.55 V drop (2.96% on 120V)
On 120V circuit2.96%
On 240V circuit1.48%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
3.55V (2.96%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 400 × 58 × 0.0766) ÷ 1000 = 3.55 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.55 ÷ 120) × 100 = 2.96%
On 240V: (3.55 ÷ 240) × 100 = 1.48%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 58A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2221V0.1851%0.0926%OK
50ft0.4443V0.3702%0.1851%OK
75ft0.6664V0.5554%0.2777%OK
100ft0.8886V0.7405%0.3702%OK
150ft1.33V1.11%0.5554%OK
200ft1.78V1.48%0.7405%OK
300ft2.67V2.22%1.11%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 58A at 400 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 58A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG3.55V2.96%1.48%OK
4/0 AWG2.82V2.35%1.18%OK
250 kcmil2.39V1.99%0.9957%OK
300 kcmil1.99V1.66%0.8294%OK
350 kcmil1.7V1.42%0.7095%OK
500 kcmil1.2V0.9976%0.4988%OK

Frequently Asked Questions

3/0 AWG carrying 58A over 400ft has a 3.55V drop (2.96% on 120V). Reference: 1.48% on 240V.
On 120V, this run sits at 2.96%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.48% on 240V versus 2.96% on 120V.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.96% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.