What Is the Voltage Drop for 3/0 AWG at 62A and 25 Feet?

3/0 AWG copper carrying 62 amps over 25 feet on a single-phase / DC circuit drops 0.2375 volts (0.1979% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3/0 AWG, 62A, 25ft · single-phase / DC
0.2375 V drop (0.1979% on 120V)
On 120V circuit0.1979%
On 240V circuit0.0989%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
0.24V (0.20%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 62 × 0.0766) ÷ 1000 = 0.2375 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.2375 ÷ 120) × 100 = 0.1979%
On 240V: (0.2375 ÷ 240) × 100 = 0.0989%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 62A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2375V0.1979%0.0989%OK
50ft0.4749V0.3958%0.1979%OK
75ft0.7124V0.5937%0.2968%OK
100ft0.9498V0.7915%0.3958%OK
150ft1.42V1.19%0.5937%OK
200ft1.9V1.58%0.7915%OK
300ft2.85V2.37%1.19%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 62A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 62A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG0.2375V0.1979%0.0989%OK
4/0 AWG0.1885V0.1571%0.0785%OK
250 kcmil0.1597V0.133%0.0665%OK
300 kcmil0.133V0.1108%0.0554%OK
350 kcmil0.1138V0.0948%0.0474%OK
500 kcmil0.08V0.0667%0.0333%OK

Frequently Asked Questions

3/0 AWG carrying 62A over 25ft has a 0.2375V drop (0.1979% on 120V). Reference: 0.0989% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.1979% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.1979%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.