What Is the Voltage Drop for 3/0 AWG at 65A and 175 Feet?

3/0 AWG copper carrying 65 amps over 175 feet on a single-phase / DC circuit drops 1.74 volts (1.45% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3/0 AWG, 65A, 175ft · single-phase / DC
1.74 V drop (1.45% on 120V)
On 120V circuit1.45%
On 240V circuit0.7261%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
1.74V (1.45%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 65 × 0.0766) ÷ 1000 = 1.74 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.74 ÷ 120) × 100 = 1.45%
On 240V: (1.74 ÷ 240) × 100 = 0.7261%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 65A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.249V0.2075%0.1037%OK
50ft0.4979V0.4149%0.2075%OK
75ft0.7469V0.6224%0.3112%OK
100ft0.9958V0.8298%0.4149%OK
150ft1.49V1.24%0.6224%OK
200ft1.99V1.66%0.8298%OK
300ft2.99V2.49%1.24%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 65A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 65A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG1.74V1.45%0.7261%OK
4/0 AWG1.38V1.15%0.5763%OK
250 kcmil1.17V0.9764%0.4882%OK
300 kcmil0.976V0.8133%0.4067%OK
350 kcmil0.8349V0.6958%0.3479%OK
500 kcmil0.587V0.4891%0.2446%OK

Frequently Asked Questions

3/0 AWG carrying 65A over 175ft has a 1.74V drop (1.45% on 120V). Reference: 0.7261% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.45% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.45%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.