What Is the Voltage Drop for 3/0 AWG at 92A and 50 Feet?

Running 92A through 3/0 AWG copper for 50 feet on a single-phase / DC circuit produces a 0.7047-volt drop. On a 120V source that is 0.5873%; on 240V it is 0.2936%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3/0 AWG, 92A, 50ft · single-phase / DC
0.7047 V drop (0.5873% on 120V)
On 120V circuit0.5873%
On 240V circuit0.2936%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
0.70V (0.59%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 92 × 0.0766) ÷ 1000 = 0.7047 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.7047 ÷ 120) × 100 = 0.5873%
On 240V: (0.7047 ÷ 240) × 100 = 0.2936%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 92A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3524V0.2936%0.1468%OK
50ft0.7047V0.5873%0.2936%OK
75ft1.06V0.8809%0.4405%OK
100ft1.41V1.17%0.5873%OK
150ft2.11V1.76%0.8809%OK
200ft2.82V2.35%1.17%OK
300ft4.23V3.52%1.76%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 92A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 92A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG0.7047V0.5873%0.2936%OK
4/0 AWG0.5594V0.4661%0.2331%OK
250 kcmil0.4738V0.3948%0.1974%OK
300 kcmil0.3947V0.3289%0.1645%OK
350 kcmil0.3376V0.2814%0.1407%OK
500 kcmil0.2374V0.1978%0.0989%OK

Frequently Asked Questions

3/0 AWG carrying 92A over 50ft has a 0.7047V drop (0.5873% on 120V). Reference: 0.2936% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.5873%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2936% on 240V versus 0.5873% on 120V.
3/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.5873% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.