What Is the Voltage Drop for 3/0 AWG at 93A and 250 Feet?

Running 93A through 3/0 AWG copper for 250 feet on a single-phase / DC circuit produces a 3.56-volt drop. On a 120V source that is 2.97%; on 240V it is 1.48%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3/0 AWG, 93A, 250ft · single-phase / DC
3.56 V drop (2.97% on 120V)
On 120V circuit2.97%
On 240V circuit1.48%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3/0 AWG
3.56V (2.97%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 93 × 0.0766) ÷ 1000 = 3.56 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.56 ÷ 120) × 100 = 2.97%
On 240V: (3.56 ÷ 240) × 100 = 1.48%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3/0 AWG at 93A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3562V0.2968%0.1484%OK
50ft0.7124V0.5937%0.2968%OK
75ft1.07V0.8905%0.4452%OK
100ft1.42V1.19%0.5937%OK
150ft2.14V1.78%0.8905%OK
200ft2.85V2.37%1.19%OK
300ft4.27V3.56%1.78%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 93A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 93A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3/0 AWG3.56V2.97%1.48%OK
4/0 AWG2.83V2.36%1.18%OK
250 kcmil2.39V2%0.9978%OK
300 kcmil1.99V1.66%0.8312%OK
350 kcmil1.71V1.42%0.7111%OK
500 kcmil1.2V0.9997%0.4999%OK

Frequently Asked Questions

3/0 AWG carrying 93A over 250ft has a 3.56V drop (2.97% on 120V). Reference: 1.48% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.48% on 240V versus 2.97% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.97%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.