What Is the Voltage Drop for 3 AWG at 13A and 500 Feet?

3 AWG copper carrying 13 amps over 500 feet on a single-phase / DC circuit drops 3.19 volts (2.65% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3 AWG, 13A, 500ft · single-phase / DC
3.19 V drop (2.65% on 120V)
On 120V circuit2.65%
On 240V circuit1.33%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3 AWG
3.19V (2.65%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 13 × 0.245) ÷ 1000 = 3.19 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.19 ÷ 120) × 100 = 2.65%
On 240V: (3.19 ÷ 240) × 100 = 1.33%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3 AWG at 13A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1593V0.1327%0.0664%OK
50ft0.3185V0.2654%0.1327%OK
75ft0.4778V0.3981%0.1991%OK
100ft0.637V0.5308%0.2654%OK
150ft0.9555V0.7963%0.3981%OK
200ft1.27V1.06%0.5308%OK
300ft1.91V1.59%0.7963%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 13A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 13A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG3.19V2.65%1.33%OK
2 AWG2.52V2.1%1.05%OK
1 AWG2V1.67%0.8342%OK
1/0 AWG1.59V1.32%0.6608%OK
2/0 AWG1.26V1.05%0.5238%OK
3/0 AWG0.9958V0.8298%0.4149%OK

Frequently Asked Questions

3 AWG carrying 13A over 500ft has a 3.19V drop (2.65% on 120V). Reference: 1.33% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.65%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.33% on 240V versus 2.65% on 120V.
3 AWG already sits within the 3% branch-circuit drop target at these inputs (2.65% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.