What Is the Voltage Drop for 3 AWG at 18A and 300 Feet?

3 AWG copper carrying 18 amps over 300 feet on a single-phase / DC circuit drops 2.65 volts (2.21% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3 AWG, 18A, 300ft · single-phase / DC
2.65 V drop (2.21% on 120V)
On 120V circuit2.21%
On 240V circuit1.1%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3 AWG
2.65V (2.21%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 18 × 0.245) ÷ 1000 = 2.65 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.65 ÷ 120) × 100 = 2.21%
On 240V: (2.65 ÷ 240) × 100 = 1.1%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3 AWG at 18A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2205V0.1838%0.0919%OK
50ft0.441V0.3675%0.1838%OK
75ft0.6615V0.5513%0.2756%OK
100ft0.882V0.735%0.3675%OK
150ft1.32V1.1%0.5513%OK
200ft1.76V1.47%0.735%OK
300ft2.65V2.21%1.1%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 18A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 18A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG2.65V2.21%1.1%OK
2 AWG2.1V1.75%0.873%OK
1 AWG1.66V1.39%0.693%OK
1/0 AWG1.32V1.1%0.549%OK
2/0 AWG1.04V0.8703%0.4351%OK
3/0 AWG0.8273V0.6894%0.3447%OK

Frequently Asked Questions

3 AWG carrying 18A over 300ft has a 2.65V drop (2.21% on 120V). Reference: 1.1% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.1% on 240V versus 2.21% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3 AWG already sits within the 3% branch-circuit drop target at these inputs (2.21% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.