What Is the Voltage Drop for 3 AWG at 26A and 250 Feet?
3 AWG copper carrying 26 amps over 250 feet on a single-phase / DC circuit drops 3.19 volts (2.65% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 3 AWG at 26A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.3185V | 0.2654% | 0.1327% | OK |
| 50ft | 0.637V | 0.5308% | 0.2654% | OK |
| 75ft | 0.9555V | 0.7963% | 0.3981% | OK |
| 100ft | 1.27V | 1.06% | 0.5308% | OK |
| 150ft | 1.91V | 1.59% | 0.7963% | OK |
| 200ft | 2.55V | 2.12% | 1.06% | OK |
| 300ft | 3.82V | 3.19% | 1.59% | Caution |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 26A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 26A load are listed, since thinner gauges would fail the ampacity check before drop even matters.