What Is the Voltage Drop for 3 AWG at 68A and 50 Feet?

Running 68A through 3 AWG copper for 50 feet on a single-phase / DC circuit produces a 1.67-volt drop. On a 120V source that is 1.39%; on 240V it is 0.6942%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3 AWG, 68A, 50ft · single-phase / DC
1.67 V drop (1.39% on 120V)
On 120V circuit1.39%
On 240V circuit0.6942%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3 AWG
1.67V (1.39%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 68 × 0.245) ÷ 1000 = 1.67 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.67 ÷ 120) × 100 = 1.39%
On 240V: (1.67 ÷ 240) × 100 = 0.6942%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3 AWG at 68A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.833V0.6942%0.3471%OK
50ft1.67V1.39%0.6942%OK
75ft2.5V2.08%1.04%OK
100ft3.33V2.78%1.39%OK
150ft5V4.17%2.08%Caution
200ft6.66V5.55%2.78%Past 5%
300ft10V8.33%4.17%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 68A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 68A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG1.67V1.39%0.6942%OK
2 AWG1.32V1.1%0.5497%OK
1 AWG1.05V0.8727%0.4363%OK
1/0 AWG0.8296V0.6913%0.3457%OK
2/0 AWG0.6576V0.548%0.274%OK
3/0 AWG0.5209V0.4341%0.217%OK

Frequently Asked Questions

3 AWG carrying 68A over 50ft has a 1.67V drop (1.39% on 120V). Reference: 0.6942% on 240V.
On 120V, this run sits at 1.39%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.6942% on 240V versus 1.39% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.