What Is the Voltage Drop for 3 AWG at 70A and 50 Feet?

3 AWG copper carrying 70 amps over 50 feet on a single-phase / DC circuit drops 1.72 volts (1.43% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3 AWG, 70A, 50ft · single-phase / DC
1.72 V drop (1.43% on 120V)
On 120V circuit1.43%
On 240V circuit0.7146%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3 AWG
1.72V (1.43%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 70 × 0.245) ÷ 1000 = 1.72 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.72 ÷ 120) × 100 = 1.43%
On 240V: (1.72 ÷ 240) × 100 = 0.7146%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3 AWG at 70A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.8575V0.7146%0.3573%OK
50ft1.72V1.43%0.7146%OK
75ft2.57V2.14%1.07%OK
100ft3.43V2.86%1.43%OK
150ft5.15V4.29%2.14%Caution
200ft6.86V5.72%2.86%Past 5%
300ft10.29V8.58%4.29%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 70A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 70A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG1.72V1.43%0.7146%OK
2 AWG1.36V1.13%0.5658%OK
1 AWG1.08V0.8983%0.4492%OK
1/0 AWG0.854V0.7117%0.3558%OK
2/0 AWG0.6769V0.5641%0.282%OK
3/0 AWG0.5362V0.4468%0.2234%OK

Frequently Asked Questions

3 AWG carrying 70A over 50ft has a 1.72V drop (1.43% on 120V). Reference: 0.7146% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.43%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
3 AWG already sits within the 3% branch-circuit drop target at these inputs (1.43% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.7146% on 240V versus 1.43% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.