What Is the Voltage Drop for 3 AWG at 7A and 75 Feet?

Running 7A through 3 AWG copper for 75 feet on a single-phase / DC circuit produces a 0.2573-volt drop. On a 120V source that is 0.2144%; on 240V it is 0.1072%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

3 AWG, 7A, 75ft · single-phase / DC
0.2573 V drop (0.2144% on 120V)
On 120V circuit0.2144%
On 240V circuit0.1072%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3 AWG
0.26V (0.21%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 7 × 0.245) ÷ 1000 = 0.2573 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.2573 ÷ 120) × 100 = 0.2144%
On 240V: (0.2573 ÷ 240) × 100 = 0.1072%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3 AWG at 7A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0858V0.0715%0.0357%OK
50ft0.1715V0.1429%0.0715%OK
75ft0.2573V0.2144%0.1072%OK
100ft0.343V0.2858%0.1429%OK
150ft0.5145V0.4287%0.2144%OK
200ft0.686V0.5717%0.2858%OK
300ft1.03V0.8575%0.4287%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 7A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 7A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG0.2573V0.2144%0.1072%OK
2 AWG0.2037V0.1698%0.0849%OK
1 AWG0.1617V0.1348%0.0674%OK
1/0 AWG0.1281V0.1067%0.0534%OK
2/0 AWG0.1015V0.0846%0.0423%OK
3/0 AWG0.0804V0.067%0.0335%OK

Frequently Asked Questions

3 AWG carrying 7A over 75ft has a 0.2573V drop (0.2144% on 120V). Reference: 0.1072% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
3 AWG already sits within the 3% branch-circuit drop target at these inputs (0.2144% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.2144%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.