What Is the Voltage Drop for 3 AWG at 87A and 25 Feet?
Running 87A through 3 AWG copper for 25 feet on a single-phase / DC circuit produces a 1.07-volt drop. On a 120V source that is 0.8881%; on 240V it is 0.4441%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 3 AWG at 87A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 1.07V | 0.8881% | 0.4441% | OK |
| 50ft | 2.13V | 1.78% | 0.8881% | OK |
| 75ft | 3.2V | 2.66% | 1.33% | OK |
| 100ft | 4.26V | 3.55% | 1.78% | Caution |
| 150ft | 6.39V | 5.33% | 2.66% | Past 5% |
| 200ft | 8.53V | 7.11% | 3.55% | Past 5% |
| 300ft | 12.79V | 10.66% | 5.33% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 87A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 87A load are listed, since thinner gauges would fail the ampacity check before drop even matters.