What Is the Voltage Drop for 3 AWG at 95A and 25 Feet?

3 AWG copper carrying 95 amps over 25 feet on a single-phase / DC circuit drops 1.16 volts (0.9698% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

3 AWG, 95A, 25ft · single-phase / DC
1.16 V drop (0.9698% on 120V)
On 120V circuit0.9698%
On 240V circuit0.4849%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

3 AWG
1.16V (0.97%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 95 × 0.245) ÷ 1000 = 1.16 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.16 ÷ 120) × 100 = 0.9698%
On 240V: (1.16 ÷ 240) × 100 = 0.4849%

How This Estimate Changes with Run Length and Gauge

Gauge Check

3 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 3 AWG at 95A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.16V0.9698%0.4849%OK
50ft2.33V1.94%0.9698%OK
75ft3.49V2.91%1.45%OK
100ft4.66V3.88%1.94%Caution
150ft6.98V5.82%2.91%Past 5%
200ft9.31V7.76%3.88%Past 5%
300ft13.97V11.64%5.82%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 95A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 95A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG1.16V0.9698%0.4849%OK
2 AWG0.9215V0.7679%0.384%OK
1 AWG0.7315V0.6096%0.3048%OK
1/0 AWG0.5795V0.4829%0.2415%OK
2/0 AWG0.4593V0.3828%0.1914%OK
3/0 AWG0.3639V0.3032%0.1516%OK

Frequently Asked Questions

3 AWG carrying 95A over 25ft has a 1.16V drop (0.9698% on 120V). Reference: 0.4849% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.9698%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
3 AWG already sits within the 3% branch-circuit drop target at these inputs (0.9698% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.4849% on 240V versus 0.9698% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.