What Is the Voltage Drop for 4/0 AWG at 106A and 300 Feet?

Running 106A through 4/0 AWG copper for 300 feet on a single-phase / DC circuit produces a 3.87-volt drop. On a 120V source that is 3.22%; on 240V it is 1.61%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 106A, 300ft · single-phase / DC
3.87 V drop (3.22% on 120V)
On 120V circuit3.22%
On 240V circuit1.61%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
3.87V (3.22%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 106 × 0.0608) ÷ 1000 = 3.87 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.87 ÷ 120) × 100 = 3.22%
On 240V: (3.87 ÷ 240) × 100 = 1.61%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 106A over 300ft on 120V is 250 kcmil. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 106A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3222V0.2685%0.1343%OK
50ft0.6445V0.5371%0.2685%OK
75ft0.9667V0.8056%0.4028%OK
100ft1.29V1.07%0.5371%OK
150ft1.93V1.61%0.8056%OK
200ft2.58V2.15%1.07%OK
300ft3.87V3.22%1.61%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 106A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 106A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG3.87V3.22%1.61%Caution
250 kcmil3.28V2.73%1.36%OK
300 kcmil2.73V2.27%1.14%OK
350 kcmil2.33V1.95%0.9726%OK
500 kcmil1.64V1.37%0.6837%OK
750 kcmil1.09V0.9063%0.4531%OK

Frequently Asked Questions

4/0 AWG carrying 106A over 300ft has a 3.87V drop (3.22% on 120V). Reference: 1.61% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This run is at 3.22% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 106A over 300ft on 120V, the smallest gauge in our table that clears it is 250 kcmil at 2.73%. Going up one size from 4/0 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
On 120V, this run sits at 3.22%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.