What Is the Voltage Drop for 4/0 AWG at 116A and 125 Feet?

Running 116A through 4/0 AWG copper for 125 feet on a single-phase / DC circuit produces a 1.76-volt drop. On a 120V source that is 1.47%; on 240V it is 0.7347%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 116A, 125ft · single-phase / DC
1.76 V drop (1.47% on 120V)
On 120V circuit1.47%
On 240V circuit0.7347%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.76V (1.47%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 116 × 0.0608) ÷ 1000 = 1.76 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.76 ÷ 120) × 100 = 1.47%
On 240V: (1.76 ÷ 240) × 100 = 0.7347%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 116A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3526V0.2939%0.1469%OK
50ft0.7053V0.5877%0.2939%OK
75ft1.06V0.8816%0.4408%OK
100ft1.41V1.18%0.5877%OK
150ft2.12V1.76%0.8816%OK
200ft2.82V2.35%1.18%OK
300ft4.23V3.53%1.76%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 116A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 116A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.76V1.47%0.7347%OK
250 kcmil1.49V1.24%0.6223%OK
300 kcmil1.24V1.04%0.5184%OK
350 kcmil1.06V0.8869%0.4435%OK
500 kcmil0.7482V0.6235%0.3118%OK
750 kcmil0.4959V0.4133%0.2066%OK

Frequently Asked Questions

4/0 AWG carrying 116A over 125ft has a 1.76V drop (1.47% on 120V). Reference: 0.7347% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.47% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.47%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.